Inrush current limiter for DIN rail mounting. Limits the starting current of electronic ballasts and LED drivers to 33.9 A for 300 ms, an acceptable value for circuit protection.
Module for mounting on 35 mm DIN rail in accordance with DIN 50022, space required: 2 HP
Connection terminals 0.5-6
Peak current limit: 48 A (± 6%)
RMS current limit: 33.9 A (± 6%)
Max. capacitive load: 6000 µF
Nominal AC voltage: 230 V AC
Nominal AC current: 16 A
Limiting speeds: 3 cycles / minute
Automatic cutout: 13 A / 16 A
Internal safety: Temperature fuse against overload